Page 1 - Ferro-Resonant Charger

EF – SERIES Installation and Operation Manual Ferro-Resonant Charger Sales – Service – Recycling Toll Free: U.S.A. 1-888-563-6300 Canada

Page 2

9When the battery is 80% charged, the charger starts phase 2 of the charge cycle. When a charge is finished, the charger automatically turns off. Th

Page 3 - Page Section Description

102.1.8 Viewing Charge Information Additional charge information is available any time by pressing the INFO button. This information is retained af

Page 4 - SAFETY INSTRUCTIONS

11 2.1.9 Charge Indications The following indications are not necessarily a result of a charger problem. They are typically caused by external pro

Page 5

12 Note: F3 and F4 clear automatically if the battery voltage falls within acceptable limits. All indications except F8, F9 and F10 can be cleared b

Page 6 - POWER TRANSFORMER SETTING

132.1.12 Programming To enter programming mode, press and hold the EDIT button and while holding it, press the INFO button. The display shows a mess

Page 7

14SECTION 2 – OPERATION (continued) 2.2 046-0372 CONTROL 2.2.1 DESCRIPT ION The 046-0372 charger control provides fully automatic battery charging in

Page 8 - 1.8 Charging Rate Adjustment

046-0372 Setup 12/9/09 047-0175 EXIDE REV04 Page 15 of 31 Press SET, then 5, then START. The display shows ‘CHARGE ALGORITHM’ followed by ‘AL:’ and

Page 9 - 2.1.4 Normal Daily Charge

046-0372 Setup 12/9/09 047-0175 EXIDE REV04 Page 16 of 31 the desired setting (0: count down, 1: count up) and press ENTER to save it. If the dire

Page 10 - 2.1.7 Auto- Refresh Charge

Table 1. Programmable Parameter List First Key Second Key Third KeyParameter(s) Description Allowable Settings Default Notes Locked SET SET none n

Page 11

Table 2. Algorithm List Algorithm Battery Type Charger Type Algorithm Type Description 1 Flooded Controlled Ferro Normal DVDT Phase 1: Consta

Page 13 - 2.1.11 Jumper Settings

10 Any Controlled Ferro Shop Charger Phase 1: Constant current at the start rate until the float voltage is reached or for the total run time.

Page 14 - 2.1.12 Programming

2.2.6 OPERA TION If alert messages are turned on, periodically a message shows for about 2 seconds in the display. With no battery connected, the

Page 15 - 2.2 046-0372 CONTROL

2.2.7.3 TOBI® PI OPERATION The control has the ability to communicate with a Tobi® PI battery module. In order for communication to occur, it ha

Page 16

2.2.7.4 CHARGE INDICATIONS The following indications are not necessarily a result of a charger problem. They are typically caused by external pr

Page 17

Note: F3 and F4 clear automatically if the battery voltage falls within acceptable limits. All indications except F8, F9 and F10 can be cleared b

Page 18

2.2.8.9 Display Charger Identification Number Chargers that are part of an I’m Cool Battery Selection System or a TOBi® Battery Management Syste

Page 19 - Table 2. Algorithm List

SECTION 3 - OPTIONAL FEATURES 3.1 Fusible Door-Interlock Switch (JIC Switch) The door interlock switch assembly connects the AC service to the ch

Page 20

4.3. AC fuse blows. POSSIBLE CAUSE A. Incorrect fuse rating. B. Incorrect AC voltage. C. Fuse Block holding clips loose. D. Shorted transfor

Page 21

SECTION 5 – REPLACEABLE PARTS 5.1 Ordering Information The following information must be supplied when ordering a replacement part from your se

Page 22

5.3 Spare Parts List Part Number Description Condensers 008-0002 2 MFD 440 Volt 008-0004 4 MFD 440 Volt 008-0006

Page 23

2INDEX Page Section Description 3 - Safety Instructions 4 1.0 Installation 4 1.1 Receiving 4 1.2 Location 4 1.

Page 24

Three Phase Charger Schematic # 02-400

Page 25

Single Phase Charger Schematic # 02-416

Page 26

3 SAFETY INSTRUCTIONS WARNING THIS EQUIPMENT CONTAINS LETHAL VOLTAGE LEVELS. INSTALLATION AND SERVICING MUST BE PERFORMED BY QUALIFIED PERSONNEL

Page 27

4 SECTION 1 - INSTALLATION 1.1. Receiving Immediately upon receipt of the charger, check it against the shipping invoice to ensure the shipment is

Page 28 - 5.2 Recommended Spares

5575POWER TRANSFORMER SETTING480L2 L2123456123456L1 L11234 132 4CONTROLTRANSFORMERCONTROLTRANSFORMERNOTE: When a 120/208/240 AC input unit is set f

Page 29 - 5.3 Spare Parts List

6 TABLE 1-1 Line Amperes Disconnect Switch Fuse Size Amps 000.0 - 02.5 30A 05 003.0 - 04.5 30A 07 005.0 - 07.5 30A 10 0

Page 30

7 1.6 Grounding the Charger The charger must be grounded to the AC system ground for personnel safety. The green ground wire in the AC input wiring

Page 31

8SECTION 2 - OPERATION The charger utilizes a standard ferro-resonant transformer, which provides isolation from the AC service line and regulates t